What are PERA Data Flows?


Chapter 4 of the Purdue Reference Model for CIM provides an example set of data flows and function hierarchies for a generic manufacturing enterprise.

These address production control, procurement, process support engineering, maintenance management, and other functions directly associated with manufacturing. It does not address "external" (to the plant) functions such as marketing and sales, finance, corporate management, and research and development. It does however, define interfaces to these functions. Only those functions which are "automatable" in the forseeable future. That is, functions which can be defined in mathematical or program terms. It does not address manufacturing functions which require human innovation.

The following diagram (Figure 4-3 of the Purdue Model for CIM) shows an overview of these data flows.

Click to Enlarge Overview Data Flow Diagram
dataflowoverview.gif - 8632 Bytes

Each of the Functions shown in the Overview is then expanded in more detailed flow diagrams such as the following Maintenance Data Flow Diagram (Figure 4-8 of the Purdue Reference Model for CIM) .

Click to Enlarge Maintenance Data Flow Diagram
dataflowmaint.gif - 6197 Bytes

In addition to data flows, this diagram also presents a set of "functions", indicating how these functions are distributed among different organizational levels. This is sometimes called a hierarchical function model".

The Purdue Reference Model for CIM is 250 pages long, and may be downloaded from this website in its entirety, or by chapter.


SITEWIDE IT AND ICS NETWORK DATAFLOWS

Design of data-flows between programs and data bases is evaluated, often in the form of "block data-flow diagrams". An example is shown in Figure 2.

arch_dat.gif - 10.8 K

Application programs must be positioned at the appropriate level in the information architecture to satisfy the Response, Resolution, Reliability, and Resilience requirements of the application.

The positioning of applications is very dependent upon the requirements of that particular plant and site. It is quite possible that a given application might exist at level 3 in one plant, and at level 4 or 5 in another. Also, most applications span several levels. Possible "multi-level" examples include quality management, production reporting, material tracking, and maintenance.

Clearly, several different applications operating at different levels may require access to the same piece of production information (eg. input flow rate). It is not practical to have each system independently request this piece of data from the level 1 device to which the sensor is connected.

In most cases, access of data is primarily from an application which is one level higher in the architecture. However, this is not always the case. For example, a level 5 engineering system may require one minute averages (Level 2) for the purpose of process unit studies. Similarly, Level 5 cost information may be provided to Level 2 or 3 optimization algorithms. None-the-less, inquiries spanning more than one level are the exception, and in general the network should be designed to optimize communications between adjacent Levels.

As data moves up through the architecture, it tends to become increasingly summarized. It also concentrates from many devices and data highways at the lowest levels, to a single production database at level 4. This Level 4 system also provides the "gateway" through which the "office systems" view the plant data, and through which plant systems view "office" information. Interestingly, as data moves up from Level 4, it tends to "fan out" again, into various commercial and technical systems. The Level 4 Database is therefore a "nexus" for all data moving from, or to, the operations level.



We welcome your Comments and Suggestions

Back to PERA Home Page